Field Setting of Indoor Unit
1.2
Setting Contents and Code No. – SkyAir Indoor Unit
Indoor
Mode
Setting
Switch
unit
No.
No.
settings
Note 2
10(20)
0
Filter contamination heavy/
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there is
heavy filter contamination.)
1
Long life filter type
2
Thermostat sensor in remote controller
3
Display time to clean air filter
calculation (Set when filter sign is not
to be displayed.)
11(21)
0
Setting of the number of units for multi-
unit simultaneous operation
1
Individual setting for multi-unit
simultaneous operation
2
Indoor unit fan OFF when cooling/
heating is OFF
4
PMV Control
12(22)
3
Fan speed when heating thermostat
OFF
5
Automatic restart after power outage
reset
6
Fan speed when cooling thermostat
OFF
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.)
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
3
Air flow direction adjustment (Set at
installation of decoration panel.)
4
Field set air flow position setting
5
Field set fan speed selection
(fan speed control by air discharge
outlet for phase control)
6
External static pressure setting (To be
set according to connected duct
resistance)
15(25)
1
Humidification when heating
thermostat is OFF
3
Drain pump humidifier interlock
selection
5
Field set selection for individual
ventilation setting by remote controller
8
Field set selection for humidifier control
by humidity sensor
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
3. Marked
4. Do not make settings other than those described above. Nothing is displayed for functions
5. "88" may be displayed to indicate the remote controller is resetting when returning to the
26
Setting Contents
Super
long life
filter
Long life
filter
Standard
filter
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
they cannot be set individually. Setting changes also cannot be checked.
are factory set.
the indoor unit is not equipped with.
normal mode.
Second Code No.(Note 3)
01
02
Light
Approx.
Heavy
Approx.
10,000
5,000
hrs.
Approx.
Approx.
2,500
1,250
hrs.
Approx.
Approx.
200
hrs.
Long life filter
Ultra long life
filter
Use
No use
Display
No display
Pair
Twin
Group
Individual
(Normal)
Fan OFF
Permitted
Prohibited
LL
Set Fan Speed
OFF
ON
LL
Set Fan Speed
N
H
F (4 directions)
T (3 directions)
Equipped
Not equipped
Draft prevention
Standard
Standard
Optional
accessory 1
Standard
High Static
(Standard)
Pressure (High
Ceiling Setting)
Not equipped
Equipped
Individual
Interlock
Not equipped
Equipped
Not equipped
Equipped
03
hrs.
hrs.
100
hrs.
Triple
Double Twin
S
W (2 directions)
Ceiling Soiling
prevention
Optional
accessory 2
Low Static
Pressure
SiBE26-701
04
Field Setting