Daikin SkyAir RZQ200 · 250C7Y1B Service Manual page 214

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701
Step
4. Remove the heat
exchanger's distribution
pipe thermistor
1
Cut the clamps
(2 places) for the heat
shield.
Pull hard the heat
2
exchanger's distribution
pipe thermistor together
with the fixing bracket
toward you.
5. Remove the heat
exchanger's intermediate
temperature thermistor
Cut the clamps
1
(2 places) for the heat
shield.
Push the lower part of
2
the fixing spring to pull
out the heat
exchanger's
intermediate
temperature thermistor.
Removal Procedure
Procedure
Heat exchanger's intermediate
temperature thermistor (R5T)
Heat exchanger's distribution
pipe thermistor (R4T)
RZQ200 · 250C7Y1B
Points
Removal of the heat
exchanger's distribution pipe
thermistor
Capillary tube
Heat exchanger's
distribution pipe
thermistor
Fixing bracket
Removel of the heat
exchanger's intermediate
temperature thermistor
Mounting
spring
bottom
Thermistor
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents