Aj" Malfunction Of Capacity Determination Device - Daikin SkyAir RZQ200 · 250C7Y1B Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Diagnosis by Remote Controller

4.10 "AJ" Malfunction of Capacity Determination Device

AJ
Remote
controller display
Applicable
FAQ, FCQ, FFQ, FHQ, FUQ
Models
Method of
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
Malfunction
is determined.
Detection
Malfunction
Operation and:
Decision
When the capacity code is not contained in the PC board's memory, and the capacity setting
adaptor is not connected.
Conditions
Supposed
Causes
Troubleshooting
114
You have forgotten to install the capacity setting adaptor.
Defect of indoor unit PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
The indoor
unit PC board was replaced
with a replacement
PC board.
YES
Was the
capacity setting
adapter mounted when
replacing the
PC board?
NO
NO
YES
SiBE26-701
Replace the indoor unit PC board.
Replace the indoor unit PC board.
Install a capacity setting adaptor.
(V2783)
Troubleshooting