Diagnosis by Remote Controller
4.21 "F3" Malfunction of Discharge Pipe Temperature
F3
Remote
Controller
Display
Applicable
RZQ
Models
Method of
Abnormality is detected according to the temperature detected by the discharge pipe
Malfunction
temperature sensor.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
130
When the discharge pipe temperature rises to an abnormally high level (115°C)
When the discharge pipe temperature rises suddenly
After operation start, the discharge pipe temperature dose not rise.
Faulty discharge pipe thermistor
Faulty connection of discharge pipe thermistor
Insufficient refrigerant amount
Faulty compressor
Disconnection of discharge pipe temperature thermistor piping