Procedure to Remove Thermistor

4. Procedure to Remove Thermistor
Procedure
Step
1
For the details of the
removal of the
thermistor for outdoor
air temperature (R1T),
see the points to the
right.
2
Pull out the discharge
pipe thermistor after
inclining the mounting
spring outward.
Thermistor for suction pipe 2 (R5T)
Thermistor for discharge pipe (R2T)
3
Pull out the thermistor
for suction pipe 1 and
thermistor for suction
pipe 2, after inclining
the mounting spring
outward.
4
Pull out the subcooling
thermistor and
thermistor for liquid
pipe, after inclining the
mounting spring
outward.
5
Pull out the thermistor
for heat exchanger after
pulling the fixing metal
part.
6
Pull out the thermistor
for liquid pipe after
inclining the mounting
spring outward.
14
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Thermistor for liquid
pipe (R7T)
Preliminary preparation
[Procedure to remove thermistor
for outdoor air temperature]
Hooks (2 places)
Thermistor for
subcooling (R6T)
Thermistor for
suction pipe 1 (R3T)
Thermistor for heat
exchanger (R4T)
Si341211
Points
Remove the front panel (2)
and side panel according to
the "Procedure to Remove
Outside Panels".
Side panel
Side panel
Notch
Fixing plate for thermistor (R1T)
Stopper
Insert
direction
Thermistor for outdoor
air temperature
Marking (yellow color)
When passing the thermistor
for outdoor air temperature
gain through the outside
panel, do it through the hole
nearby attached with a
yellow color mark.
Removal Procedure