SiBE26-701
3.2

Maintenance Mode Setting

3.2.1 Service Data Confirmation
Procedure
1. Enter the field set mode.
2. Enter the service mode.
3. Select the mode No.
4. Select the unit No.
5. Select the necessary settings for each mode. (Modes 40 or 41)
6. Select the desired malfunction hysteresis of sensor data display with
7. Return to the normal operation mode.
Table
Mode
No.
40
41
Remote Controller
5
4
1, 2, 7
3
Continue to push the inspection / test operation button for a minimum of 4 seconds.
After having entered the field set mode, continue to push the inspection / test operation
button for a minimum of 4 seconds.
Set the desired mode No. with the up/down temperature setting button.
Select the indoor unit No. set with the TIME MODE START/STOP button.
(In case of wireless remote controller, use
Each data displays (Refer below display)
Press the inspection / test operation button one time.
Function
Content and Operation Method Example of Remote Controller Display
Malfunction
You can change the history
Hysteresis
with the programming time up-
down button.
Sensor Data
Select the display sensor with
Display
the programming time up-
down button
Display sensor
00 Remote control sensor
01 Suction
02 Heat exchange
Method of Operating Remote Controller
or
button.)
or
button.
19