Daikin SkyAir RZQ200 · 250C7Y1B Service Manual page 152

R-410a heat pump 50hz
Table of Contents

Advertisement

SiBE26-701
Troubleshooting
1: Voltage measurement point
2: "Pressure Sensor", pressure/voltage characteristics table.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check if the connector for
the low-pressure sensor
(X31A) is correctly
connected to the outdoor
unit PC board (A1P)
Is it connected
correctly?
YES
Measure the voltage (V)
between the pins # (2) and
(3) of the above connector
(∗1).
YES
Is the relation
between the pressure and the
voltage normal?
(∗2).
NO
NO
YES
1.5
PL
1.0
0.5
0
-0.5
-0.5
0
0.5
1
1.5
2
2.5
Output voltage V
PL
=
0.57V-0.28
PL
: Detected pressure (MPa)
V
: Output Voltage (V)
Diagnosis by Remote Controller
Connect correctly
Replace outdoor unit PC board
(A1P).
Replace the low pressure sensor.
3
3.5
4
Vcc
(V2808)
141