Field Setting of Outdoor Unit
Change of Setting Conditions in "Setting Mode 2"
Push and hold the MODE (BS1)
button for 5 seconds and set to
"Setting mode 2".
<Selection of setting items>
Push the SET (BS2) button and set
the LED display to a setting item
shown in the table on the right.
Push the RETURN (BS3) button and
decide the item. (The present setting
condition is blinked.)
<Selection of setting conditions>
Push the SET (BS2) button and set
to the setting condition you want.
Push the RETURN (BS3) button and
decide the condition.
Push the RETURN (BS3) button and
set to the initial status of "Setting
mode 2".
40
No. Setting Item
Additional refrigerant charge operation 8 1 1 1 1 1 1
0
1
Refrigerant recovery mode
7
Demand 1 operation
11
Defrost changeover 2 operation
13
EMG operation 3
14
Back-up operation
The numbers in the "No." column represent the number of times to press the SET (BS2)
button.
[ON/OFF] Pattern
ON
OFF
[MODE1~3] Pattern
MODE 1
MODE 2 (Factory Setting)
MODE 3
LED Display
H1P H2P H3P H4P H5P H6P H79
8 1 1 1 1 1 8
8 1 1 1 8 8 8
8 1 1 8 1 8 8
8 1 1 8 8 1 8
8 1 1 8 8 8 1
8 1 1 1 1 8 1
8 1 1 1 1 1 8
8 1 1 1 1 1 8
8 1 1 1 1 8 1
8 1 1 1 8 1 1
8: ON
1: OFF
SiBE26-701
Condition setting
pattern
ON/OFF
MODE1~3
ON/OFF
Field Setting