Procedure To Remove Low Pressure Thermistor, Electronic Expansion Valve, And Others - Daikin RZQ71KAVLT Service Manual

Removal procedure, 3 hp class, outdoor unit, inverter, pair type
Hide thumbs Also See for RZQ71KAVLT:
Table of Contents

Advertisement

Procedure to Remove Low Pressure Thermistor, Electronic Expansion Valve, and Others

7. Procedure to Remove Low Pressure Thermistor,
Electronic Expansion Valve, and Others
Procedure
Step
Remove the outside
panels, their parts, and
the switch box, following
the procedure indicated at
"Removal of Outside
Panels and Related Parts"
and other instructions.
1. Remove the pressure
thermistor
1
Remove the connector
for the pressure
thermistor (X17A).
Remove the pressure
2
thermistor after cutting
off the brazing (1
location).
2. Remove the pressure
switch
Remove the lead wire.
1
2
Remove the pressure
switch after cutting off
the brazing.
3. Remove the electronic
expansion valve
Pull out the coil from the
1
electronic expansion
valve upward.
Cut the brazing (2
2
locations) and remove
the body of the
electronic expansion
valve.
(Replace with the
assembly of the
electronic expansion
valve)
8
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Pressure thermistor
Pressure
switch
Coil of electronic
expansion valve
Body of electronic
expansion valve
Points
Brazing
Be sure to collect the
refrigerant first, before
removing the main unit of the
motor operated valve.
Precaution for the mounting
of the coil of the motor
operated valve
Clip
Press the coil into tube until the
clip completely fits in the tube.
Removal Procedure
Si281314E

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents