Daikin SkyAir RZQ200 · 250C7Y1B Service Manual page 87

R-410a heat pump 50hz
Table of Contents

Advertisement

Maintenance Inspections
Correlation of Air-
What happens in comparison to normal values is summarized in the table below.
(Measured from 15 ~ 20 minutes or more after operation starts.)
Conditioner's
Operation Status
and Pressure /
When Cooling
Running Current
Air-Conditioner Status
Air Filter Fouling
Short Circuit of Indoor Unit Inlet/
Outlet Air
Outdoor Unit Fin Fouling
Short Circuit of Outdoor Unit Inlet/
Outlet Air
Air Mixed in Refrigerant
Water Mixed in Refrigerant
Dirt Mixed in Refrigerant
Lack of Refrigerant (Gas)
Unsatisfactory Compression
When Heating
Air-Conditioner Status
Air Filter Fouling
Short Circuit of Indoor Unit Inlet/
Outlet Air
Outdoor Unit Fin Fouling
Short Circuit of Outdoor Unit Inlet/
Outlet Air
Air Mixed in Refrigerant
Water Mixed in Refrigerant
Dirt Mixed in Refrigerant
Lack of Refrigerant (Gas)
Unsatisfactory Compression
Notes:
1.
2.
3.
76
1. Water in the refrigerant freezes inside the capillary tube or expansion valve, and is
basically the same phenomenon as pump down.
2. Dirt in the refrigerant clogs filters inside the piping, and is basically the same
phenomenon as pump down.
3.Pressure differential between high and low pressure becomes slight.
Low Pressure
High Pressure
Lower
Lower
Lower
Lower
Higher
Higher
Higher
Higher
Higher
Higher
∗1 Lower
Lower
∗2 Lower
Lower
Lower
Lower
∗3 Higher
Lower
Low Pressure
High Pressure
Higher
Higher
Higher
Higher
Lower
Lower
Lower
Lower
Higher
Higher
∗1 Lower
Lower
∗2 Lower
Lower
Lower
Lower
∗3 Higher
Lower
SiBE26-701
Running Current
Lower
Lower
Higher
Higher
Higher
Lower
Lower
Lower
Lower
Running Current
Higher
Higher
Lower
Lower
Higher
Lower
Lower
Lower
Lower
Troubleshooting