Jogging Operation Function - Omron JX User Manual

200 v class three-phase input 0.2 to 7.5 kw; 200 v class single-phase input 0.2 to 2.2 kw; 400 v class three-phase input 0.4 to 7.5 kw
Table of Contents

Advertisement

4-2 Function Mode

Jogging Operation Function

The motor rotates while the input is turned ON..
Parameter No.
A038
A039
Related parameters
Required settings
4
•The Inverter runs at the speed set in A038 while the JG terminal allocated to one of the multi-
function input terminals is turned on. Stop selection is also available in A039.
Jog can be assigned to any of the multifunction inputs setting this value into C001 to C005.
Data
06
Related parameters
•If the frequency is set to a higher value, the jogging operation may easily lead to a trip. Adjust A038
so that the Inverter does not trip.
Note 1: To perform the jogging operation, turn on the JG terminal before the FW or RV terminal.
Note 2: If A039 is set to 02, set the DC injection braking.
4-14
Function name
Jogging frequency
0.00/Starting frequency to 9.99
00: Free-run stop
Jogging stop selection
01: Deceleration stop
02: DC injection braking stop
Symbol
Function name
JG
Jogging operation
(When A039 = 01)
Output frequency
A038
(Do the same if the RUN command source is set to the Digital Operator.)
JG
FW
Output
frequency
Data
C001 to C005, JG input
A002 = 01, A038 > b082, A038 > 0, A039
Status
ON
OFF
C001 to C005
JG
FW
RV
Jogging does not function if the
FW signal turns on beforehand.
Default setting
6.00
00
Description
Operates at the set jogging frequency.
Stop
Unit
Hz