Initial Setup Examples - Omron E5GN User Manual

Temperature controller
Hide thumbs Also See for E5GN:
Table of Contents

Advertisement

CHAPTER 3 BASIC OPERATION
3.1

Initial Setup Examples

F
Typical example 1
Input type
: 0 K thermocouple 200 to 1300
Control method
: ON/OFF control
Alarm type
: 2 upper limit
_
Alarm value 1
: 20
C (deviation)
_
Set point
: 100
C
3-2
On previous controllers, sensor input type, alarm type and control period
were set by the DIP switches. These hardware settings are now set in
parameters in setup menus. The
between setup menus, and the amount of time that you hold the keys down
for determines which setup menu you move to. This section describes two
typical examples.
_
Setup procedure
C
Power ON
Initial setting level
Set input specifications
Set control specifications
Set alarm type
Operation level
Set alarm values
Start operation
and
keys are used to switch
Power ON
Operation level
Press
three seconds.
Control stops.
Initial setting level
Check input type.
Check that control
is ON/OFF control.
Check alarm type.
Press
least one second.
Control starts
Operation level
Press
keys
_
to set set point to
100
C".
Make sure that
control is running.
Press
keys
_
to set alarm value
to 20
C".
Start operation
Process value/set
point
key for at least
Input type
In ON/OFF
control
In PID control
Alarm 1 type
key for at
Process value/
set point
During run
During stop
Alarm value 1