Specific Example
Output area
IR 50
For another node
IR 51
16 outputs for Unit #1
IR 52
IR 53
4 analog outputs
IR 54
for Unit #3
IR 55
IR 56
IR 57
IR 58
IR 59
IR 60
IR 61
IR 62
IR 63
For another node
HE(-Z) PC, turn ON IR 10000. For details of the DeviceNet startup proce-
dure, refer to the DeviceNet Operation Manual (W267).
10. Check the operation.
• Checking Indicators
• Checking the I/O Unit Interface Status
Example:
The following allocations will be used for status when the default alloca-
tions are used for a Communications Unit with node number 01 connected
to a C200HX/HG/HE(-Z) DeviceNet Master Unit with unit address 0.
Node
number
(First)
Unused
Unused
Unused
Unused
Unused
Unused
(Last)
Unused
• The first two words of the input area is automatically allocated for the
I/O Unit interface status information. This allocation cannot be
changed.
• Words are allocated for the input/output data for each I/O Unit in the
order that the I/O Units are connected (I/O Unit interface addresses 0
to 3) in the input area (input) and the output area (output).
• The input/output areas are allocated in the words corresponding to
node numbers 01 to 11.
With normal operations, all indicators should be lit green.
MS NS TS TS
TS
#0
#1
Input:
Output:
16 points
16 points
Input area
For another node
I/O Unit interface
status
16 inputs for Unit #0
8 analog outputs
for Unit # 2
For another node
U.ERR is
U.ERR is
TS
TS
not lit.
not lit.
#2
#3
Analog
Analog output:
input:
4 outputs
8 inputs
(words)
(words)
IR 350
Check the I/O Unit
interface status. If
IR 351
normal, the status
IR 352
will be as follows:
IR 353
IR 354
IR 351
IR 355
IR 352
IR 356
IR 357
IR 358
IR 359
IR 360
IR 361
IR 362
IR 363
Section 2-2
25