Omron DEVICENET#05-2003 Operation Manual page 137

Drt1-com gt1 series devicenet multiple i/o terminal
Table of Contents

Advertisement

Analog Output Units
Terminal Arrangement
Wiring
Output Ranges and
Converted Data
Internal power supply
External
Internal power
output
supply
The Analog Output Unit converts the digital output data to analog values. The
analog values depend on the output signal ranges, as shown in the following
diagrams.
1 to 5 V
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog
voltage range of 1 to 5 V. The entire output range is 0.8 to 5.2 V.
Voltage
5.2 V
5 V
1 V
0.8 V
0 V
FED4
0000 (0)
8000
( 300)
Voltage output
External
output
1770
189C
7FFF
(6000)
(6300)
Section 5-2
Current output
Converted data
Hexadecimal
(Decimal)
127