System Monitor Screens
!WARNING
!WARNING
Note
1,2,3...
Check the following items before starting to run the Loop Control Board:
• Do not allow the bank of the EM Area with the number specified for alloca-
tion to the HMI (human-machine interface) data to overlap with any other
area used by the CPU Unit or other Units. The block allocated for the HMI
is specified in ITEM 050 (EM Area Bank Allocated for HMI Memory = 0 to
12) of the System Common block. If areas overlap, the system may oper-
ate in an unexpected fashion, which may result in injury.
• Do not allow the area to which user link table data is written to overlap
with any other area used by the CPU Unit or other Units. If areas overlap,
the system may operate in an unexpected fashion, which may result in
injury.
• Analog Input/Output Units used in combination with the Loop Control
Board must be mounted correctly, and the unit number set on the front
panel of the Analog Input/Output Unit must match the unit number set on
the Field Terminal block. If the unit numbers do not match, input/output
(read/write) is performed on the data of another Special I/O Unit (whose
unit number is set on the Field Terminal block).
• The defaults of the System Common block on the Loop Control Board
must be set correctly.
Always stop the operation of the Loop Control Board before converting any of
the EM Area to file memory. If any part of the EM Area that is being used by
the Loop Control Board for the HMI is converted to file memory during Board
operation, the system may operate in an unexpected fashion, which may
result in injury.
First sufficiently check system operation using the CX-Process Tool (check
the load rate, etc.: Execution, Operation, Monitor Run Status), and sufficiently
check operation (Monitor Run Status, Start) for the Function Block data that
has been created, and then change to actual operation. In particular, first
check that the load rate is 60% or less, and then change to actual operation.
1. Click the number button for the Loop Control Unit you want to use, as
shown.
Click here.
The Run/Stop Command Dialog Box will be displayed as shown (for a Loop
Control Unit).
• Loop Control Unit is stopped.
Section 4-17