Exchanging Contact Signal Data - Omron CX-PROCESS MONITOR PLUS V2 - 01-2007 Operation Manual

Table of Contents

Advertisement

Data Exchange Method
3-1-4

Exchanging Contact Signal Data

Setting Bits from Monitor
Plus
1,2,3...
58
In order to read/write the Loop Control Unit or Board's contact signal data, the
Contact Distributor (Block Model 201) and Internal Switch (Block Model 209)
blocks must be registered as a set and the Contact Distributor (Block Model
201) must be connected to each function block's contact ITEMs. Set the tags
for Monitor Plus in the Internal Switch (Block Model 209) block's bits.
Loop Control Unit or Board
Contact
Function
Contact
block
Distributor
Contact
(Block
Model 201)
Contact
Function
block
Contact
1. Connect the Contact Distributor (Block Model 201) as the destination for
the function block's contact input ITEM that you want to set. At the same
time, input (connect) the Internal Switch (Block Model 209) from the Con-
tact Distributor (Block Model 201).
2. Set the tags for Monitor Plus in the Internal Switch (Block Model 209). Set
a tag name for each ITEM (S1 to S8).
Set tags for Monitor Plus.
(Select Set"to write data.)
CPU Unit
I/O memory
Write
Internal
Switch
(Block
Model 209)
Select Setting.
Section 3-1
Monitor Plus
Specify the tags
for Monitor Plus
and write data.