Omron CP - PROGRAMMING MANUAL 05-2007 Programming Manual page 1001

Cp1h/cp1l cpu unit
Table of Contents

Advertisement

Other Instructions
Variations
Applicable Program Areas
Description
968
Variations
Executed Each Cycle for ON Condition
Executed Once for Upward Differentiation
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Block program areas
OK
OK
When the execution condition is ON, FRMCV(284) executes the following
operations.
1. The CV-series PLC memory address specified in S is converted to its
equivalent CV-series data area address.
2. FRMCV(284) determines the CP-series PLC memory address that corre-
sponds to the same CV-series data area address.
3. The CP-series PLC memory address is output to D. (An index register (IR0
to IR15) must be specified for D.)
The following example shows FRMCV(284) used to convert the CV-series
PLC memory address in D0.
FRMCV
D0
IR1
D0
#2001
1. The CV-series PLC memory address is
converted to its equivalent CV-series data
area address.
CV-series PLC
memory address
2001 Hex
2. The corresponding CV-series data area
address is converted to its CP-series PLC
memory address.
CP-series data
area address
D1
3. The CP-series PLC memory
address is stored in D.
IR1
10001 Hex
Step program areas
Subroutines
OK
CV-series data
area address
D1
CP-series PLC
memory address
10001 Hex
Storage
Section 3-29
FRMCV(284)
@FRMCV(284)
Not supported.
Interrupt tasks
OK