Design
Wireless devices and other equipment that generates electromagnetic waves should never
be installed in the same control panel with the Inverter.
The DC power supply used for communications should have reinforced or double insulation.
An Inverter control terminal has only basic insulation. More insulation is required if the termi-
nal is wired to parts people are likely to touch.
H Conforming to LVD
• Always connect the Inverter and power supply via a molded case circuit breaker
(MCCB) suitable to the Inverter for protecting the Inverter from damage that may result from short-cir-
cuiting.
• Use one MCCB per Inverter.
• Select a suitable MCCB from the following table.
• With a 400-V-class Inverter, be sure to ground to a neutral point of the power supply.
200-V Models
Inverter
Model 3G3MV-
A2001
A2002
A2004
A2007
A2015
A2022
A2037
A2055
A2075
AB001
AB002
AB004
AB007
AB015
AB022
AB037
400-V Models
Inverter
Model 3G3MV-
A4002
A4004
A4007
A4015
A4022
A4037
A4055
A4075
2-40
Rated current (A)
5
5
5
10
20
20
30
50
60
5
5
10
20
20
40
50
Rated current (A)
5
5
5
10
10
20
30
30
MCCB
Type
NF30 (Mitsubishi Electric)
(
NF30 (Mitsubishi Electric)
(
MCCB
Type
NF30 (Mitsubishi Electric)
(
Chapter 2
)
)
)