Omron SYSDRIVE 3G3MV SERIES User Manual page 328

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

List of Parameters
H Function Group 4 (n120 through n179)
Param-
Regis-
Name
eter
ter No.
No.
(Hex)
n120
0178
Frequency
reference 9
n121
0179
Frequency
reference 10
n122
017A
Frequency
reference 11
n123
017B
Frequency
reference 12
n124
017C
Frequency
reference 13
n125
017D
Frequency
reference 14
n126
017E
Frequency
reference 15
n127
017F
Frequency
reference 16
n128
0180
PID control
selection
n129
0181
Feedback
value adjust-
ment gain
n130
0182
Proportional
(P) gain
n131
0183
Integral (I)
time
n132
0184
Derivative (D)
time
n133
0185
PID offset
adjustment
10-26
Description
Sets the internal frequency refer-
e ces
ences.
* These frequency references are
selected with multi-step speed ref-
selected with multi step speed ref
erences (multi-function inputs).
See the reference pages for the
g
relationship between multi-step fre-
relationship bet een m lti step fre
quency references and frequency
references.
references
Selects the PID control method.
0: PID control disabled.
1 to 8: PID control enabled.
* The derivative control method (i.e.,
the derivative control of the devi-
ation or detected value), the addi-
tion of the frequency reference,
and the positive or negative char-
acteristics of PID control are
selectable.
Sets the value by which the feedback
value is multiplied.
* This parameter is used for adjust-
ing the target and detected values
so that they will have the same
input level.
Sets the proportional (P) gain for PID
control.
* PID control is disabled with this
parameter set to 0.0.
Sets the integral (I) time for PID con-
trol.
* Integral control is disabled with this
parameter set to 0.0.
Sets the derivative (D) time for PID
control.
* Derivative control is disabled with
this parameter set to 0.0.
This parameter is for the offset adjust-
ment of all PID control.
Sets the parameter as a percentage
based on the maximum frequency as
100%.
Chapter 10
Set-
Unit
Default
Changes
ting
of
setting
range
set-
ting
0.00
0.01
0.00
Yes
Hz to
o
Hz
max.
(Cha
(C
0.00
Yes
nge-
able
able
0.00
Yes
with
n035
n035
0.00
Yes
set-
tings)
tings)
0.00
Yes
0.00
Yes
0.00
Yes
0.00
Yes
0 to 8
1
0
No
0.00 to
0.01
1.00
Yes
10.00
0.0 to
0.1
1.0
Yes
25.0
0.0 to
0.1 s
1.0
Yes
360.0
0.00 to
0.01
0.00
Yes
2.50
s
–100
1%
0
Yes
to 100
Ref-
during
er-
opera-
ence
tion
page
5-19
5-19
5-19
5-19
5-19
5-19
5-19
5-19
6-16
6-16
6-16
6-16
6-17
6-17