List of Parameters
Para
Reg-
Name
me-
ister
ter
No.
No.
(Hex)
n060
013C
Frequency
reference
gain
n061
013D
Frequency
reference
bias
n062
013E
Analog fre-
quency ref-
erence fil-
ter time
constant
n063
---
Not used
n064
0140
Frequency
reference
loss detec-
tion (See
note.)
n065
0141
Multi-func-
tion analog
output type
selection
10-18
Description
Used to set the input characteristics of analog
frequency references.
Gain: The frequency of maximum analog input
(10 V or 20 mA) in percentage based on the
(10 V or 20 mA) in percentage based on the
maximum frequency as 100%.
Bias: The frequency of minimum analog input
(0 V or 0 or 4 mA) in percentage based on the
maximum frequency as 100%.
Used to set the digital filter with a first-order lag
for analog frequency references to be input.
---
Selects the frequency loss detection function
for when the frequency reference from the con-
trol circuit terminal suddenly drops.
0: Disable (Operate according to frequency ref-
erence.)
1: Enable (Continue operation at 80% of fre-
quency reference prior to loss.)
* Frequency reference loss: Frequency refer-
ence voltage drop of 90% within 400 ms.
Selects the multi-function analog output type.
0: Analog voltage output (functions set in n066)
1: Pulse train output (functions set in n150)
Chapter 10
Set-
Unit
Defaul
Chan-
ting
of
t set-
ges dur-
range
set-
ting
ting
opera-
0 to
1%
100
Yes
255
–100
1%
0
Yes
to 100
0.00
0.01 s 0.10
Yes
to
2.00
---
---
---
---
0, 1
1
0
No
0, 1
1
0
No
Ref-
er-
ing
ence
page
tion
5-13
5-13
5-14
---
5-17
5-38