Specifications
Protec-
Motor protection
tive
i
Instantaneous
func-
overcurrent
tions
protection
Overload protection
Overvoltage
protection
Undervoltage
protection
Momentary power
interruption
compensation
(selection)
Cooling fin
overheating
Grounding
protection
Charge indicator
Environ- Location
ment
Ambient operating
temperature
Ambient humidity
Ambient storage
temperature
Altitude
Insulation
resistance
Vibration resistance 9.8 m/s
Degree of protection
Note 1. The power supply capacity is the capacity for the Inverter's rated output. It will vary depending
on the impedance at the input power supply. (This is due to fluctuations in the power factor.
The power factor can be improved by inserting an AC reactor.) There will also be variations in
the ratio between the rated current of the motor that is used and the rated output current of the
Inverter.
Note 2. The heat radiation is the electric power consumed in the Inverter at the Inverter's rated output.
Note 3. The 5.5- and 7.5-kW Inverters are closed wall-mounting models (NEMA1/IP20) as a stan-
dard, but they can be converted to panel-mounting (IP00) by removing the top and bottom
covers.
9-6
Protection by electronic thermal
Stops at approx. 250% of rated output current
Stops in 1 min at approximately 150% of rated output current
Stops when main-circuit DC voltage is approximately 820 V
Stops when main-circuit DC voltage is approximately 400 V
Stops for 15 ms or more. By setting the Inverter to momentary power
interruption mode, operation can be continued if power is restored within
approximately 0.5 s.
Detects at 110 ± 10°C
Protection at overcurrent detection level
Charge indicator until main circuit DC voltage reaches 50 V max.
Indoors (with no corrosive gas, oil spray, or metallic dust)
–10 to 50°C
Operating: 95% max. (with no condensation)
–20 to 60°C
1,000 m max.
5 MΩ min. (Do not carry out any insulation resistance or withstand
voltage tests)
2
max. between 10 to 20 Hz
2
2.0 m/s
max. between 20 and 50 Hz
Panel-mounting models: Conforms to IP20
Chapter 9
Closed
wall-mounting:
–10 to 40°C
Panel-
mounting:
–10 to 50°C
Closed
wall-mounting
(NEMA1)/
Panel- mounting
(IP00)
(See note 3.)