Frequency Jump Function (N083 To N086) - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Advanced Operation

6-10-6 Frequency Jump Function (n083 to n086)

• The frequency jump function prevents the Inverter from generating frequencies that make the
mechanical system resonate.
• The frequency jump function can be used effectively to set three dead bands of a frequency reference.
n083
Jump Frequency 1
Setting
0.00 to 400.0 (Hz)
range
n084
Jump Frequency 2
Setting
0.00 to 400.0 (Hz)
range
n085
Jump Frequency 3
Setting
0.00 to 400.0 (Hz)
range
n086
Jump Width
Setting
0.00 to 25.50 (Hz)
range
Set Values
• Set n083 through n085 for jump frequencies 1 through 3 to the central values of jumping frequencies.
• Values will be set in 0.01-Hz increments if the frequency is less than 100 Hz and 0.1-Hz increments if
the frequency is 100 Hz or over.
• These values must satisfy the following condition.
n083 y n084 y n085
• The value in n086 must be set for the jump width.
• This function is disabled with n086 set to 0.0.
• The operation of the Inverter within the dead bands is prohibited. While the Inverter is in acceleration
or deceleration control, however, the Inverter does not jump the bands but changes the frequency
smoothly.
6-42
Register
0153 Hex
Unit of
0.01 Hz
setting
Register
0154 Hex
Unit of
0.01 Hz
setting
Register
0155 Hex
Unit of
0.01 Hz
setting
Register
0156 Hex
Unit of
0.01 Hz
setting
Chapter 6
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00
Changes during
No
operation
Default setting
0.00

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents