Omron SYSDRIVE 3G3MV SERIES User Manual page 166

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Advanced Operation
• The Inverter cannot maintain rated output current with the carrier frequency set to a value higher than
the default one.
The following table shows the default settings and the reduced rated output currents resulting from a
higher setting for the carrier frequency for each Inverter model.
When the carrier frequency is set to a higher value than the default setting, use the Inverter at a current
less than the reduced rated output current.
Voltage
Model 3G3MV-
3-phase
p
A2001
200 V
200 V
A2002
A2004
A2007
A2015
A2022
A2037
A2055
A2075
Single-phase
g
p
AB001
200 V
V
AB002
AB004
AB007
AB015
AB022
AB037
3-phase
p
A4002
400 V
V
A4004
A4007
A4015
A4022
A4030
A4037
A4055
A4075
Note The rated output current can be output without reduction.
n175
Low Carrier Frequency at Low
Speed
Setting
0, 1
range
Note For 5.5- and 7.5-kW Inverters, the default setting is "1" (enable).
6-24
Default setting
Rated output
current (A)
4 (10 kHz)
0.8
4 (10 kHz)
1.6
4 (10 kHz)
3.0
4 (10 kHz)
5.0
3 (7.5 kHz)
8.0
3 (7.5 kHz)
11.0
3 (7.5 kHz)
17.5
3 (7.5 kHz)
25.0
3 (7.5 kHz)
33.0
4 (10 kHz)
0.8
4 (10 kHz)
1.6
4 (10 kHz)
3.0
4 (10 kHz)
5.0
3 (7.5 kHz)
8.0
3 (7.5 kHz)
11.0
3 (7.5 kHz)
17.5
3 (7.5 kHz)
1.2
3 (7.5 kHz)
1.8
3 (7.5 kHz)
3.4
3 (7.5 kHz)
4.8
3 (7.5 kHz)
5.5
3 (7.5 kHz)
7.2
3 (7.5 kHz)
8.6
3 (7.5 kHz)
14.8
3 (7.5 kHz)
18.0
Register
Unit of
setting
Set to 3
Reduced rated
output current
(A)
01AF Hex
Changes during
operation
1
Default setting
Chapter 6
Set to 4
Reduced rated
output current
(A)
7.0
10.0
16.5
23.0
30.0
7.0
10.0
16.5
1.0
1.6
3.0
4.0
4.8
6.3
8.1
14.8 (See note.)
17.0
No
0
(See
note.)