Setting the Carrier Frequency

The carrier frequency of the 3G3MV can be fixed or varied in proportion to the output
frequency.
n080
Carrier Frequency Selection
Setting
1 to 4, 7 to 9
range
Note The default setting varies with the capacity of the Inverter model.
Set Values
Value
1
2.5 kHz
2
5.0 kHz
3
7.5 kHz
4
10.0 kHz
7
2.5 kHz (12×): 12 times as high as output frequency (from 1.0 to 2.5 kHz)
8
2.5 kHz (24×): 24 times as high as output frequency (from 1.0 to 2.5 kHz)
9
2.5 kHz (36×): 36 times as high as output frequency (from 1.0 to 2.5 kHz)
• The default setting does not need any changes in normal operation.
• Change the default setting in the following cases.
The wiring distance between the Inverter and motor is long:
Set the Inverter to a lower carrier frequency.
Reference carrier frequency:
Note The carrier frequency changes as shown in the following graph with 7 through 9 set in n46.
Carrier Frequency (n080: 7 through 9)
Carrier
Frequency
Wiring distance ≤ 50 m:
50 m < Wiring distance ≤ 100 m:
Wiring distance > 100 m:
83.3 Hz (Set value: 7)
41.6 Hz (Set value: 8)
27.7 Hz (Set value: 9)
Register
0150 Hex
Unit of
1
setting
Description
208.3 Hz (Set value: 7)
104.1 Hz (Set value: 8)
69.4 Hz (Set value: 9)
Chapter 6
Changes during
No
operation
Default setting
(See
note.)
10 kHz
5 kHz
2.5 kHz
Output frequency
6-23