Operation
3-6-9 Selecting Reverse Rotation Prohibition
• This parameter is used to specify whether to enable or disable a reverse rotation command sent to
the Inverter.
• The parameter must be set to prohibit reverse operation when the Inverter is applied to applications
in which reverse rotation of the Inverter would cause problems.
P13
Reverse rotation prohibit selection
Selected item F.R/FWD
Selected item
F.R (f.r)
Allow reverse operation
FWD (fwd)
Prohibit reverse operation (reverse operation disabled)

3-6-10 Setting the Carrier Frequency

• With the 3G3JE, it is possible to switch between two carrier frequencies.
• Change the carrier frequency in the following cases.
Reduce the carrier frequency to 4 kHz if there are fluctuations in the speed or torque at low speeds
or if the wiring distance between the Inverter and motor is excessively long.
Wiring distance
50 m or less
Longer than 50 m
P14
Carrier frequency selection
Setting range 4/7 (kHz)
Set value
4 (4k)
4 kHz
7 (7k)
7 kHz
3-6-11 Initializing Parameters
• The parameters can be initialized to their default values.
• Parameters are initialize when P20 is set to "ini" and then the Enter Key is pressed.
• The frequency reference will also be initialized to the default value.
• The motor accumulated operating time will not be initialized.
P20
Parameter initialization
Setting range ini/abt
Set value
ini (ini)
Initialize
abt (abt)
Abort
3-22
Description
Carrier frequency (guideline)
4 kHz or 7 kHz
4 kHz
Description
Description
Chapter 3
Changes during
No
operation
Default setting
FWD
Changes during
No
operation
Default setting
4k
Changes during
No
operation
Default setting
abt