Srx5400 Firewall Grounding-Cable Lug Specification - Juniper SRX5400 Hardware Manual

Firewall
Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

WARNING: To meet safety and electromagnetic interference (EMI) requirements and to
ensure proper operation, you must properly ground the firewall chassis before
connecting power. See

SRX5400 Firewall Grounding-Cable Lug Specification

The accessory box shipped with the firewall includes the cable lug that attaches to the grounding cable
(see
Figure 16 on page
38) and two UNC 1/4–20 screws used to secure the grounding cable to the
grounding points.
Figure 16: Grounding Cable Lug
CAUTION: Before firewall installation begins, a licensed electrician must attach a cable
lug to the grounding and power cables that you supply. A cable with an incorrectly
attached lug can damage the firewall.
NOTE: The same cable lug is used for the DC power cables.
RELATED DOCUMENTATION
Calculating Power Requirements for the SRX5400 Firewall | 150
Replacing an SRX5400 Firewall DC Power Supply | 233
Replacing an SRX5400 Firewall AC Power Supply | 229
Troubleshooting the SRX5400 Firewall Power System | 331
"Grounding the SRX5400 Firewall " on page 195
for instructions.