General Site Guidelines - Juniper SRX5400 Hardware Manual

Firewall
Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

Table 29: Firewall Environmental Specifications
Description
Temperature
Seismic
Maximum thermal output
NOTE: Install the firewall only in restricted areas, such as dedicated equipment rooms and
equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.

General Site Guidelines

Efficient device operation requires proper site planning and maintenance. It also requires proper layout
of the equipment, rack or cabinet, and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally
caused equipment failures:
• Keep the area around the chassis free from dust and conductive material, such as metal flakes.
• Follow prescribed airflow guidelines to ensure that the cooling system functions properly. Ensure
that exhaust from other equipment does not blow into the intake vents of the device.
• Follow the prescribed electrostatic discharge (ESD) prevention procedures to prevent damaging the
equipment. Static discharge can cause components to fail completely or intermittently over time.
• Install the device in a secure area, so that only authorized personnel can access the device.
(Continued)
Value
Normal operation ensured in temperature range of 32°F (0°C) to 104°F (40°C)
Nonoperating storage temperature in shipping container: –40°F (–40°C) to
158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake requirements
AC power: 8065 BTU/hour (2365 W)
DC power: 7325 BTU/hour (2148 W)
145

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srx5600Srx5800

Table of Contents