Table 15: AC Power Supply LEDs
Label
Color
State
AC OK
Amber
Off
Green
On
DC OK
Green
Off
On
PS FAIL
Red
Off
On

AC Power Cord Specifications for the SRX5400 Firewall

Each AC power supply has a single AC appliance inlet located on the power supply that requires a
dedicated AC power feed. Most sites distribute power through a main conduit that leads to frame-
mounted power distribution panels, one of which can be located at the top of the rack that houses the
firewall. An AC power cord connects each power supply to the power distribution panel.
The firewall is not shipped with AC power cords. You must order power cords separately using the
model number shown in
on page
29, inserts into the AC appliance inlet coupler, type C20 (right angle) as described by
International Electrotechnical Commission (IEC) standard 60320. The plug end of the power cord fits
into the power source receptacle that is standard for your geographical location.
Description
AC power input voltage is below 78 VAC.
AC power input voltage is within 78–264 VAC.
DC power outputs generated by the power supply are not within the normal
operating ranges.
DC power outputs generated by the power supply are within the normal operating
ranges.
Power supply is functioning normally.
Power supply is not functioning normally and its output voltage is out of regulation
limits. Check AC OK and DC OK LEDs for more information.
Table 16 on page
29. The C19 appliance coupler end of the cord see
28
Figure 11