Omron NT31C Reference Manual page 433

Hide thumbs Also See for NT31C:
Table of Contents

Advertisement

Specifications
Element
Analogue meter
Broken line graphs
Trend graphs
Alarm lists
Alarm history
• Restrictions due to element coefficients
The PT uses element coefficients to manage display elements. The maximum number of display coefficients
that can be used at the same time is 1024.
If the total of the element coefficients on a screen exceeds 1024, the elements after this total has been reached
are not displayed.
The element coefficients for each element are indicated in the table below. Ensure that the total for the screen to
be displayed is not greater than 1024.
Element
Fixed displays (text,
graphics)
Image data
Library data
Marks
Touch switches
Lamps
Numeral inputs
Character string inputs
Thumbwheel switches
Numeral displays
Character string displays
Recipe
Bar graphs
Analogue meter
Broken line graphs
Trend graphs
426
One numeral memory table
When numeral memory tables are designated for each of the –100%,0%, and 100%
settings for each graph line, one numeral memory table is read for each of these
settings.
Number of numeral memory tables determined by number of graph lines
vertices
When numeral memory tables are designated for each of the –100%, 0%, and 100%
settings for each graph line, one numeral memory table is read for each of these
settings.
Data logging function not used
Data logging function used
Number of bit memory tables referenced.
None
1, regardless of how many there are on the screen
1
1
1 (or 2 if there is a cursor moving key touch switch) + number of dedicated touch
switches
1 (or 2 if there is a cursor moving key touch switch) + number of dedicated touch
switches
1 + number of displayed digits
1
1
1 + number of lines in name field + number of lines in parameters field + number of
dedicated touch switches
1
1
1
1 + number of dedicated touch switches
Restriction on Read Data
Number of numeral memory tables determined by
the number of graph lines
When numeral memory tables are designated for
each of the –100%, 0%, and 100% settings for
each graph line, one numeral memory table is
read for each of these settings.
Number of background memory tables
determined by the number of graph lines
When numeral memory tables are designated for
each of the –100%, 0%, and 100% settings for
each graph line, one numeral memory table is
read for each of these settings.
Element Coefficient
2
Appendix A
number of