Enabling/Disabling PT Operations
Controlling the Enabling/Disabling of PT Side Operation by Operation at the PT
Status Control Area
Setting
Operation
15
14
13
12
11
10
9
8
0
356
Use this method to enable and disable PT operations from the host. PT opera-
tions that can be controlled include opening windows, inputting numeric values
and character strings, and switching screens.
The PT status control area must be allocated to a word in the host, accordingly,
no special settings are required for reading the operation at the PT.
Bits used to control the PT status (PT status control bits) are provided at the
fourth word (word n + 3) from the beginning in the PT status control area.
• Bit 6: Enabling/disabling the PT side window opening
• Bit 5: Enabling/disabling the inputting of numeric values and character strings
• Bit 4: Enabling/disabling the PT side screen switching
7
6
5
4
3
2
1
0
0
To control the operation by the PT while it is running, operate the PT status con-
trol area in the manner shown below.
Change the setting of the bits in the fourth word (word n + 3) from the beginning in
the PT status control area as indicated below according to the required control.
word n + 3
• Bit 6:
To control the PT side window opening
• Bit 5:
To control the inputting of numeric values and character strings
• Bit 4:
To control PT side screen switching
To disable operation:
To enable operation:
Bit
Controlled Item
15
Screen display
14
Processing priority registration (for NT link (1:N))
13
Continuous buzzer
12
Intermittent buzzer (short)
11
Display history initialization
10
Not used
9
Intermittent buzzer (long)
8
Backlight mode
7
Screen printing
6
PT window opening
5
Numeral/character string input
4
PT screen switching
3
Memory table copy execution
2
Memory table copy type
1
Alarm history initialization
0
Not used
Bits 2 and 3 are not used when the PT is in NT30/620
compatible mode.
1 (ON)
0 (OFF)
Section
3-12
1 (ON)
0 (OFF)
Performed
Not performed
Registered
Canceled
Sounded
Stopped
Sounded
Stopped
Performed
Not performed
Always 0
Sounded
Stopped
Lit
Flashing
Performed
Not performed
Disabled
Enabled
Disabled
Enabled
Disabled
Enabled
Performed
Not performed
Numeral
Character string
Performed
Not performed
Always 0