DC Power Supplies
Each DC power supply has a handle, an ejection lever, a status LED, and a terminal block that provides a
single DC input (24, –48, or –60 VDC and return) that requires a dedicated customer site circuit breaker.
We recommend that you provide at least 17 A @ 24 VDC and use a facility circuit breaker rated for 16.5
A minimum, or as required by local code.
Figure 11: DC Power Supply
SEE ALSO
Connecting AC Power Cords to the ACX4000 Router | 102
Connecting DC Power Cables to the ACX4000 Router | 104

ACX4000 Power Consumption

The power supply in an ACX4000 router is built along the front panel of the chassis, with a DC power
terminal on the front to connect power to the router.
Table 17 on page 61
lists the power consumed by the ACX4000 router.
Figure 11 on page 60
shows the power supply.