• Be sure to connect the ground wire or conduit to a solid office (earth) ground. A closed loop ring is
recommended for terminating the ground conductor at the ground stud.
• A DC-powered router that is equipped with a DC terminal block is intended only for installation in a
restricted access location. In the United States, a restricted access area is one in accordance with
Articles 110-16, 110-17, and 110-18 of the National Electrical Code ANSI/NFPA 70.
NOTE: Primary overcurrent protection is provided by the building circuit breaker. This breaker
should protect against excess currents, short circuits, and earth faults in accordance with NEC
ANSI/NFPA70.
• Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
• For personal safety, connect the green and yellow wire to safety (earth) ground at both the router
and the supply side of the DC wiring.
• The marked input voltage of –48 VDC for a DC-powered router is the nominal voltage associated
with the battery circuit, and any higher voltages are only to be associated with float voltages for the
charging function.
• Because the router is a positive ground system, you must connect the positive lead to the terminal
labeled +, the negative lead to the terminal labeled –, and the earth ground to the chassis grounding
points.
RELATED DOCUMENTATION
DC Power Copper Conductors Warning | 193
DC Power Disconnection Warning | 193
DC Power Grounding Requirements and Warning | 195
DC Power Wiring Sequence Warning | 195
DC Power Wiring Terminations Warning | 197