Calibration; Calibration: Reference Method - Siemens SITRANS LU150 Operating Instructions Manual

Ultrasonic transmitters
Table of Contents

Advertisement

Commissioning

5.2 Calibration

5.2
Calibration
The calibration of the mA output may be done such that its span will be either proportional or
inversely proportional to the material level.
Note
The 4 and 20 mA levels may be calibrated in any order.
5.3

Calibration: reference method

1. Adjust the material level (or target) to the desired distance from the sensor face.
2. Press the "4" or "20" key (as appropriate) to view the stored distance associated with that mA
output value.
3. Press the key a second time to set the new distance reference.
4. After viewing or calibrating, the unit operation automatically reverts to the Run mode (6 sec).
The calibration value is referenced from the face of SITRANS LU150 sensor, in the units
displayed.
22
Proportional span
high level = 20 mA
low level = 4 mA
Inversely proportional span
high level = 4 mA
low level = 20 mA
Operating Instructions, 03/2016, A5E34590123-AB
SITRANS LU150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents