Connecting Power to an AC-Powered Junos Pulse Gateway

76
You ground the device by connecting a grounding cable to earth ground and then attaching
it to the chassis grounding points, using UNC 1/4-20 two screws. You must provide the
grounding cables (the cable lugs are supplied with the device).
Verify that a licensed electrician has attached the cable lug provided with the device
1.
to the grounding cable.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
2.
the strap to an approved site ESD grounding point. See the instructions for your site.
Ensure that all grounding surfaces are clean and brought to a bright finish before
3.
making grounding connections.
Connect the grounding cable to a proper earth ground.
4.
Detach the ESD grounding strap from the site ESD grounding point.
5.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
6.
the strap to one of the ESD points on the chassis.
Place the grounding cable lug over the grounding points on the upper rear of the
7.
chassis. The bolts are sized for UNC 1/4-20 bolts.
Secure the grounding cable lug to the grounding points, first with the washers, and
8.
then with the screws.
Dress the grounding cable, and verify that it does not touch or block access to device
9.
components, and that it does not drape where people could trip on it.
Connecting Power to an AC-Powered Junos Pulse Gateway on page 76
You connect AC power to the device by attaching power cords from the AC power sources
to the AC appliance inlets located on the power supplies of the Junos Pulse Gateway.
The power cords are provided with the Junos Pulse Gateway.
To connect the AC power cords to the device for each power supply:
Locate or obtain the power cords you will use with the Junos Pulse Gateway. The
1.
power cords must have a plug appropriate for your geographical location.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
2.
the strap to one of the ESD points on the chassis.
Insert the appliance coupler end of the power cord into the inlet on the power supply
3.
on the back panel of the Junos Pulse Gateway chassis.
Insert the power cord plug into an external AC power source receptacle.
4.
NOTE:
Each power supply must be connected to a dedicated AC power
feed and a dedicated external circuit breaker. We recommend that you
use a 15 A (250 VAC) minimum, or as permitted by local code.