Copyright © 2015, Juniper Networks, Inc.
A cable with an incorrectly attached lug can damage the router (for
example, by causing a short circuit).
To meet safety and electromagnetic interference (EMI) requirements and
to ensure proper operation, you must connect the chassis to earth ground
before you connect it to power. For installations that require a separate
grounding conductor to the chassis, use the protective earthing terminal
on the router chassis to connect to the earth ground. For instructions on
connecting earth ground, see
Router" on page
Install the power supply in the chassis. For instructions on installing a power supply in
a ACX5000 router, see
"Installing a Power Supply in an ACX5000 Router" on page
Ensure that you have the following parts and tools available:
DC power source cables (14–16 AWG) with ring lug (Molex 190700069 or equivalent)
(not provided)
Phillips (+) screwdriver, number 2 (not provided)
Multimeter (not provided)
To connect DC power to an ACX5000 router:
Attach the grounding strap to your bare wrist and to a site ESD point.
1.
Verify that the DC power cables are correctly labeled before making connections to
2.
the power supply. In a typical power distribution scheme where the return is connected
to chassis ground at the battery plant, you can use a multimeter to verify the resistance
of the –48V and RTN DC cables to chassis ground:
The cable with very low resistance (indicating a closed circuit) to chassis ground is
positive (+) and will be installed on the V+ (return) DC power input terminal.
The cable with very high resistance (indicating an open circuit) to chassis ground
is negative (–) and will be installed on the V– (input) DC power input terminal.
CAUTION:
You must ensure that power connections maintain the proper
polarity. The power source cables might be labeled (+) and (–) to indicate
their polarity. There is no standard color coding for DC power cables. The
color coding used by the external DC power source at your site determines
the color coding for the leads on the power cables that attach to the DC
power input terminals on each power supply.
Ensure that the input circuit breaker is open so that the voltage across the DC power
3.
source cable leads is 0 V and that the cable leads do not become active while you
are connecting DC power.
Chapter 11: Connecting the Router to Power
"Connecting Earth Ground to an ACX5000
112.
137.
117

Advertisement

loading

This manual is also suitable for:

Acx5096Acx5000Acx5048-acAcx5048-dcAcx5096-acAcx5096-dc