[:Input]:Scaling:{Vt|Ct|Sfactor}:Element<X; [:Input]:Synchronize - Teledyne Everywhereyoulook T3PM1100 User Manual

Digital power meter
Hide thumbs Also See for Everywhereyoulook T3PM1100:
Table of Contents

Advertisement

Return parameter 0
Example
[:INPut]:SCALing:{VT|CT|SFACtor}:ELEMen
t<x>
Description
Syntax
Query Syntax
Parameter/
Return parameter
Example

[:INPut]:SYNChronize

Description
Syntax
Query Syntax
Parameter/
Return parameter
154
Turn the scaling function off.
1
Turn the scaling function on.
:INPUT:SCALING:STATE ON
:INPUT:SCALING:STATE?
->:INPUT:SCALING:STATE 1
Sets or returns the VT ratio, CT ratio, or power
coefficient of the specified element.
[:INPut]:SCALing:{VT|CT|SFACtor}:ELEMent<x>
{<NRf>}
[:INPut]:SCALing:{VT|CT|SFACtor}:ELEMent<x>?
<x>
1(If <Element> is omitted, the element
is
set to 1)( For the T3PM1100, only set to
1
or omitted)
<NRf>
0.001 to 9999
:INPUT:SCALIG:VT:SRATIO:ELEMENT1 10
:INPUT:SCALIG:VT:SRATIO:ELEMENT1?
->:INPUT:SCALIG:VT:SRATIO:ELEMENT1 10
Sets or returns the synchronization source.
[:INPut]:SYNChronize {VOLTage|CURRent|OFF}
[:INPut]:SYNChronize?
VOLTage
Select the voltage synchronization
source.
T3PM1100 User Manual
Set
Query
Set
Query

Advertisement

Table of Contents
loading