Equipment and cable installation for 1665 Data Multiplexer
(1665 DMX)
........................................................................................................................................................................................................................
Label the feeders at the BDCBB or BDFB as follows:
7
1. BAT A
2. BAT A RTN
3. BAT B
4. BAT B RTN
Important!
circuit breaker on the shelf. For the BDFB, the fuse rating should be 1.5 times the
rating of the circuit breaker on the shelf.
........................................................................................................................................................................................................................
Leave the BDCBB breakers off or BDFB fuses out until you are ready to perform the
8
procedures in
Multiplexer (1665 DMX)"
........................................................................................................................................................................................................................
Check off the appropriate box in
9
E
O
N D
........................................................................................................................................................
............................................................................................................................................................................................................................................................
1 - 2 4
Each feeder at the BDCBB should be rated 1.25 times the rating of the
Chapter 2, "Powering and initial circuit pack installation for 1665 Data
of this manual.
S
F
T E P S
Appendix E, "Installation
Power cable and cable bracket installation
checklist".
Issue 1, November 2007
365-372-304R7.1