Equipment and cable installation for 1665 Data Multiplexer
(1665 DMX)
........................................................................................................................................................................................................................
Cut the office alarm cable to the desired length.
4
........................................................................................................................................................................................................................
Wire-wrap the loose end of the office alarm cable to the alarm panel, making connections
5
as listed in
E
O
N D
........................................................................................................................................................
Alarm mult
The following steps should be performed when the bottom shelf in the bay will be directly
connected to the office alarms. The cable added in this procedure is to mult office alarms
in a bay to the bottom shelf. In this procedure the bottom shelf is multed to the shelf
immediately above. That shelf is then multed to the shelf above it. Continue until the top
shelf is connected.
Important!
reported, all office alarm cable mults from that shelf to the bottom shelf must be in
place. No shelf should be skipped.
........................................................................................................................................................................................................................
Obtain the office alarm mult cable (848589602 for DMX to DMX and 848861530 for
1
DMX to Lambda Unite). Connect one end to ALM MULT (J13) of the 1665 DMX High-
Capacity shelf.
........................................................................................................................................................................................................................
Route the office alarm mult cable to the side of the bay and connect it to ALM (J12) of the
2
1665 DMX High-Capacity shelf above or to Lambda Unite as required.
............................................................................................................................................................................................................................................................
1 - 8 0
Table 1-21, Office alarm
S
F
T E P S
In order for office alarms in a shelf (other than the bottom shelf) to be
connections.
Office alarm cable installation
365-372-304R7.1
Issue 1, November 2007