Installation tests

Local equipment and cross-connect tests

............................................................................................................................................................................................................................................................
Description
The tests in this section verify the proper operation of the circuit packs and the circuit pack
positions in the 1665 DMX shelf. It verifies proper cabling from the 1665 DMX to the
DSX cross-connect panel or connecting equipment. The shelf must successfully pass this
test before testing any other feature of the 1665 DMX.
It is assumed that
Multiplexer (1665 DMX)"
back cables on the Main OLIUs with proper LBOs installed, and synchronization set to
free-running.
On initial installation/turn-up of 1665 DMX there are no default cross-connects. All cross-
connects need to be entered for these tests. Upon completion of this test all cross-
connections will be deleted.
Important!
function slots and repeat the test. Test all circuit pack positions which have DSX
cabling.
Important!
isolate and replace any failed units. If any cabling is corrected or units replaced, repeat
the Local Equipment and cross-connect tests until the units pass without failure.
A properly grounded ESD wrist strap MUST be worn when handling circuit packs.
Unterminated optical connectors may emit laser radiation. Do not view beam with
optical instruments.
............................................................................................................................................................................................................................................................
365-372-304R7.1
Issue 1, November 2007
Chapter 2, "Powering and initial circuit pack installation for 1665 Data
has been completed and the 1665 DMX shelf has fiber loop-
If the shelf is not fully equipped, move circuit packs to unequipped
After completing this test, isolate and correct any incorrect wiring or
CAUTION
ESD hazard
WARNING
Laser hazard
Local equipment and cross-connect tests
4 - 9