Operational tests

Miscellaneous (environmental) discrete telemetry test

............................................................................................................................................................................................................................................................
Description
Miscellaneous discrete telemetry access allows the maintenance center to control and
monitor equipment co-located with the 1665 DMX shelf. Perform this procedure for
shelves that are cabled for miscellaneous discrete telemetry.
........................................................................................................................................................................................................................
Miscellaneous discrete telemetry test procedure
........................................................................................................................................................................................................................
Determine which environmental inputs are to be monitored via the 1665 DMX shelf.
1
........................................................................................................................................................................................................................
Verify that the miscellaneous discrete cable is connected to the J11 MISC connector on the
2
shelf. See
........................................................................................................................................................................................................................
3
Refer to
(p. 5-18)
input to be tested.
........................................................................................................................................................................................................................
At the far end of the cable, short the associated environmental input lead to the red-slate
4
(R-S) Input Common lead.
........................................................................................................................................................................................................................
Verify that the minor (MN) alarm lights on the SYSCTL.
5
........................................................................................................................................................................................................................
From the system view click Alarm List.
6
Result:
........................................................................................................................................................................................................................
7
Remove the short and verify that the minor (MN) alarm indication on the SYSCTL clears.
........................................................................................................................................................................................................................
Repeat
8
............................................................................................................................................................................................................................................................
5 - 1 6
Figure 5-1, "1665 DMX Shelf Backplane" (p.
Table 5-2, "Miscellaneous (Environmental) Discrete Telemetry Connections"
to determine the wire color of the cable lead associated with the environmental
Verify that the correct environmental alarm has been activated.
Step 3
through
Step 7
Miscellaneous (environmental) discrete telemetry test
for each environmental input being used.
5-14).