Operational tests
........................................................................................................................................................................
................................................................................................................................................
12
Reconnect the timing cable at the rear of the shelf.
Requirement: The MN LED extinguishes on the SYSCTL and the FAULT LED on
the OLIU stops flashing.
................................................................................................................................................
13
Check off the appropriate box in
E
O
N D
........................................................................................................................................................

Miscellaneous (environmental) discrete telemetry test

Description
Miscellaneous discrete telemetry access allows the maintenance center to control and
monitor equipment co-located with the Alcatel-Lucent 1665 DMX shelf. Perform this
procedure for shelves that are cabled for miscellaneous discrete telemetry.
Miscellaneous discrete telemetry test procedure
................................................................................................................................................
1
Determine which environmental inputs are to be monitored via the Alcatel-Lucent 1665
DMX shelf.
................................................................................................................................................
2
Verify that the miscellaneous discrete cable is connected to the J11 MISC connector on the
shelf. See
................................................................................................................................................
3
See
Table 7-2, "Miscellaneous (environmental) discrete telemetry connections" (p. 7-16)
to determine the wire color of the cable lead associated with the environmental input to be
tested.
................................................................................................................................................
4
At the far end of the cable, short the associated environmental input lead to the red-slate
(R-S) Input Common lead.
................................................................................................................................................
5
Verify that the minor (MN) alarm lights on the SYSCTL.
........................................................................................................................................................................
7 - 1 4
S
F
T E P S
Figure 7-1, "Alcatel-Lucent 1665 DMX shelf backplane" (p.
Miscellaneous (environmental) discrete telemetry test
Table I-3, Installation acceptance
checklist.
7-13).
Alcatel-Lucent 1665 DMX R9.0
365-372-304R9.0 Issue 2
July 2010