Output Specifications - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

5.4

Output Specifications

This sections describes the output specifications of the CPU module.
Relay output
Item
Number of Output Points
Connection type
Output type
External power supply
Max. load
Min. load
Open circuit leakage current
Off  On
Response time
On  Off
Indication of output operation
*1 Area-specific model
*2 When two common terminals are connected outside the I/O module, resistance load is 8A or less.
• FX5S CPU module, FX5UJ CPU module, and FX5U CPU module circuit configuration
Item
Relay output
5 CPU MODULE PERFORMANCE SPECIFICATIONS
94
5.4 Output Specifications
Output specifications
FX5S
FX5UJ
FX5S-30MR: 14 points
FX5UJ-24MR: 10 points
FX5S-40MR: 16 points
FX5UJ-40MR: 16 points
FX5S-60MR: 24 points
FX5UJ-60MR: 24 points
*1
FX5S-80MR
: 32 points
Non-removable terminal
Removable terminal block (M3 screws)
block (M3 screws)
Relay
30VDC or less
240VAC or less (250VAC or less if not a CE, UL, cUL compliant item)
2A/point
The total load current per common terminal should be the
following value.
• 3 output points/common terminal: 6A or less
• 4 output points/common terminal: 8A or less
For details on the common, refer to Page 101 Power,
input/output terminal block.
5VDC, 2mA (reference values)
Approx. 10ms
Approx. 10ms
LED turns on when output is on.
Circuit configuration diagram
Load
DC power supply
Fuse
Load
AC power supply
Fuse
A common number is inserted into
FX5U
FX5U-32MR: 16 points
FX5U-64MR: 32 points
FX5U-80MR: 40 points
2A/point
The total load current per
common terminal should be
the following value.
• 4 output points/common
terminal: 8A or less
• 8 output points/common
terminal: 8A or less
For details on the common,
refer to Page 101
Power, input/output terminal
block.
Y
COM
Y
COM
of [COM
].
FX5UC
FX5UC-32MR/DS-TS: 16
points
Spring clamp terminal block
2A/point
The total load current per
common terminal should be
the following value.
• 8 output points/common
*2
terminal: 4A or less
For details on the common,
refer to Page 101
Power, input/output terminal
block.

Advertisement

Table of Contents
loading

Table of Contents