I/O MODULES REPLACEMENT

3.2.2 Output module specifications comparison

(1) Specifications comparison between A0J2-E24R and QY10
Specifications
Number of output points
Insulation method
Rated switching voltage/
current
Minimum switching load
Maximum switching
voltage
OFFON
Response
time
ONOFF
Mechanical life
Electrical life
Maximum switching
frequency
Common terminal
arrangement
Operation indication
External
Voltage
supply
power
(relay coil
Current
driving
power)
3
- 15
A0J2-E24R
24 points
Photocoupler
24VDC 2A (Resistance load)/
24VDC 2A (Resistance load)/
point
240VAC 2A (COS=1)/ point
5A/common
5VDC 1mA
264VAC, 125VDC
10ms or less
12ms or less
20 million times or more
Rated switching
voltage/current load
200,000 times or more
(COS=0.7) 100,000 times or
(COS=0.7) 300,000 times or
200 VAC 1.5A, 240 VAC 1A
(COS=0.7) 200,000 times or
more
(COS=0.35) 100,000 times or
200VAC 0.75A, 240VAC 0.5A
(COS=0.35) 200,000 times or
200VAC 0.3A, 240VAC 0.15A
more
(COS=0.35) 300,000 times or
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 200,000 times or
more
24VDC 0.3A, 100VDC 0.03A
3600 times/hr
8 points/common
(Common terminal: TB9, TB19,
TB29)
Available (Turning ON the output
turns LED ON)
24VDC±10%
Ripple voltage 4Vp-p or less
230mA (TYP. 24VDC All points
are ON.)
: Compatible,
QY10
Compatibility
16 points
Relay
point
240VAC 2A (COS = 1)/ point
8A/common
5VDC 1mA
264VAC, 125VDC
10ms or less
12ms or less
20 million times or more
Rated switching
voltage/current load
100,000 times or more
200VAC 1.5A, 240VAC 1A
more
200VAC 0.4A, 240VAC 0.3A
more
200VAC 1A, 240VAC 0.5A
more
more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 100,000 times or
more
(L/R=7ms) 300,000 times or
more
3600 times/hr
16 points/common
(Common terminal: TB17)
ON indication (LED)
: Partially changed, × : Incompatible
Precautions for replacement
When seventeen or more points
are used, use two QY10 modules.
Although the insulation methods
differ, the performance of the
Insulation is the same.
Reduce the exchange intervals of
the modules as Mechanical/
Electrical Life is cut to about half.
As the common changes from
three commons to a common,
wiring with a different voltage for
each common is not possible.
External supply power is not
required.