Wire end treatment
Treat stranded and solid wires as they are or use wire ferrules with insulation sleeves for wiring terminals.
■When stranded and solid wires are treated as they are
• Twist the end of stranded wires, and make sure that there are no loose wires.
• Do not solder-plate the electric wire ends.
Stripping dimensions of electric wire ends
Built-in analog I/O terminal block, built-in RS-485
communication terminal block
5mm
■When wire ferrules with insulation sleeves are used
Depending on the thickness of a wiring sheath used, inserting the sheath into an insulation sleeve may be difficult. Refer to
the external dimensions as a reference to select wires.
Built-in analog I/O terminal block, built-in RS-485
communication terminal block
Insulation sleeve
Contact
(crimped part)
6mm
2 to 2.5mm
10.5 to 12mm
<Reference>
Product
Built-in analog I/O terminal block
Terminal block for built-in RS-485
communications
Expansion board, expansion adapter
■Tool
For tightening terminals, use a small screwdriver with a straight tip that is not widened toward the end as shown below.
With straight tip
0.4mm
2.5mm
Precautions
When a precision screwdriver with a small grip is used, the specified tightening torque cannot be obtained. Use the following
screwdriver or equivalent product (grip diameter: 25mm) to obtain the tightening torque specified above.
<Reference>
Manufacturer
Phoenix Contact GmbH & Co. KG
Manufacturer
Phoenix Contact GmbH & Co. KG
Expansion board, expansion adapter
9mm
Expansion board, expansion adapter
Insulation sleeve
Contact
(crimped part)
8mm
2.6mm
14mm
Model
AI 0.5-6 WH
AI 0.5-8 WH
Model
SZS 0.42.5
13.2 Preparation of Wiring Components
Crimp tool
CRIMPFOX 6
CRIMPFOX 6T-F
13 WIRING