REPLACEMENT OF I/O MODULE

3.2.2 Comparison of output module specifications

(1) Specifications comparison between A1SY10 and QY10
Specifications
Number of output points
Isolation method
Rated switching voltage/
current
Minimum switching load
Maximum switching
voltage
Off  on
Response
time
On  off
Mechanical
Life
Electrical
Maximum switching
frequency
Surge suppressor
Common terminal
arrangement
Operation indication
Fuse
External
Voltage
power
supply
Current
External connection
system
Applicable wire size
Applicable solderless
terminal
Current consumption
External dimensions
Weight
A1SY10
16 points
Photocoupler
24VDC 2A (resistance load)/point
240VAC 2A (COS=1)/point
8A/common
5VDC 1mA
264VAC
125VDC
10ms or less
12ms or less
20 million times or more
Rated switching voltage/
current load
100,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7) 100,000 times or more
200VAC 1A, 240VAC 0.5A
(COS=0.35) 100,000 times or more
24VDC 1A,100VDC 0.1A
(L/R=7ms) 100,000 times or more
3600 times/hr
None
8 points/common
(common terminal: TB9, TB18)
On indication (LED)
None
24VDC±10%
Ripple voltage 4Vp-p or less
90mA (typ. 24VDC, all points on)
20-point terminal block
connector (M3.57 screws)
2
0.75 to 1.25mm
R1.25-3.5, R2-3.5,
RAV1.25-3.5, RAV2-3.5
0.12A (typ. all points on)
130(H)34.5(W)93.6(D)mm
0.25kg
: Compatible,
QY10
16 points
Relay
24VDC 2A (resistance load)/point
240VAC 2A (COS=1)/point
8A/common
5VDC 1mA
264VAC
125VDC
10ms or less
12ms or less
20 million times or more
Rated switching voltage/
current load
100,000 times or more
200VAC 1.5A, 240VAC 1A
(COS=0.7)100,000 times or more
200VAC 0.4A, 240VAC 0.3A
(COS=0.7) 300,000 times or more
200VAC 1A, 240VAC 0.5A
(COS=0.35) 100,000 times or more
200VAC 0.3A, 240VAC 0.15A
(COS=0.35) 300,000 times or more
24VDC 1A, 100VDC 0.1A
(L/R=7ms) 100,000 times or more
24VDC 0.3A, 100VDC 0.03A
(L/R=7ms) 300,000 times or more
3600 times/hr
None
16 points/common
(common terminal: TB17)
On indication (LED)
None
-
-
18-point terminal block
(M36 screws)
2
Core: 0.3 to 0.75mm
(outside diameter: 2.8mm or less)
R1.25-3
(Sleeved solderless terminal cannot
be used.)
0.43A (typ. all points on)
98(H)27.4(W)90(D)mm
0.22kg
: Partially changed, : Incompatible
Compat-
Precautions for replacement
ibility
The isolation method differs, but
the performance is the
equivalent.
-
As the common is changed from
2 commons to 1 common, wiring
with a different voltage for each
common is not possible.
-
An external power supply is not
required.
Wiring change is required.
Review the current capacity since
the current consumption is
increased.
Wiring space is narrower.