Specifications when used at an operating ambient temperature below 0
For using the device at an operating ambient temperature below 0, specifications are different from when using it at an
operating ambient temperature of 0 to 55.
Item
Capacity of 24VDC
FX5U-32M/E
service power supply
of the CPU module
(AC power supply
specifications)
FX5U-64M/E
FX5U-80M/E
Supply capacity when 24VDC service power
supply is used for the input circuit of the
CPU module
Supply capacity when external power supply
is used for the input circuit of the CPU
module
Supply capacity when 24VDC service power
supply is used for the input circuit of the
CPU module
Supply capacity when external power supply
is used for the input circuit of the CPU
module
Supply capacity when 24VDC service power
supply is used for the input circuit of the
CPU module
Supply capacity when external power supply
is used for the input circuit of the CPU
module
When used at 0 to 55
When used at below 0
400mA
300mA
480mA
380mA
600mA
300mA
740mA
440mA
600mA
300mA
770mA
470mA