Output Wiring Example - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Output wiring example

Relay output
■FX5S CPU module, FX5UJ CPU module, and FX5U CPU module
AC power supply 100 to 240V
Breaker
Power supply input
PL
MC
MC
Emergency
stop
MC
DC power
supply
Power supply for load connected to
programmable controller output
Emergency stop operation is in
accordance with "Design precautions"
in "Safety precautions".
*1 The output circuit of the programmable controller does not have a built-in fuse.
Provide a fuse suitable for each load to prevent melting of the wires on the circuit board caused by output device breakdown due to load
short-circuiting.
*2 "" represents vacant terminals.
13 WIRING
200
13.6 Output Wiring
MC
*1
Fuse
COM0
Y0
*1
Fuse
COM1
Y4
*1
Fuse
COM3
Y14
*2
*1
Fuse
COM0
Y0
Y7
Load
*1
Fuse
COM1
Y0
Y7
Load
CPU module
relay output
Output module
relay output

Advertisement

Table of Contents
loading

Table of Contents