Mitsubishi Electric MELSEC iQ-F Series User Manual page 56

Programmable
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Precautions
• When CC-Link IE Field Network Basic is used, remote I/O points that are used in CC-Link IE Field Network Basic are
occupied, and then remote I/O points of the intelligent function module are occupied. For information on CC-Link IE Field
Network Basic, refer to CC-Link IE Field Network Basic Reference Manual.
• When using the CC-Link master (FX3U-16CCL-M) and AnyWireASLINK master (FX3U-128ASL-M) together, connect the
FX3U-128ASL-M before (on the left side of) the CC-Link master. In the FX5U CPU module, the FX3U-16CCL-M
parameters are set up by programmable controller program, and up to 256 remote I/O points are occupied (including
vacant points). Therefore, when the FX3U-16CCL-M is connected before (on the left side), the number of remote I/O points
that can be used by the FX3U-128ASL-M that is connected after (on the right side) may be less than 128 points.
Ex.
When the number of I/O points is 160 points, the FX3U-16CCL-M is connected before (on the left side of) the FX3U-128ASL-
M, and 256 points of the remote I/O points to be used by the FX3U-16CCLM are occupied: 512 points - 160 points - 256 points
= 96 points
Remote I/O points that can be used with the FX3U-128ASL-M are 96 points or less.
Number of I/O points on whole system : 512 points
Number of I/O points : 160 points
Expansion board,
expansion adapter
Ex.
When the number of I/O points is 160 points, the FX3U-16CCL-M is connected after (on the right side of) the FX3U-128ASL-
M, and the total number of remote I/O points to be used by the FX3U-128ASL-M is 128: 512 points - 160 points - 128 points =
224 points
Remote I/O points that can be used with the FX3U-16CCL-M are 224 points or less.
Number of I/O points on whole system : 512 points
Number of I/O points : 160 points
Expansion board,
expansion adapter
2 SYSTEM CONFIGURATION
54
2.3 System Configuration Specifications
FX5U
I/O module
CPU module
FX5U
I/O module
CPU module
Intelligent
CC-Link master
module
System on CC-Link
Number of remote I/O points
: 256 points
Remote I/O
station
Intelligent
AnyWireASLINK master
module
System on AnyWireASLINK
Number of remote I/O points
: 128 points
Remote I/O
station
AnyWireASLINK master
System on AnyWireASLINK
Number of remote I/O points
: 96 points
Remote I/O
station
CC-Link master
System on CC-Link
Number of remote I/O points
: 224 points
Remote I/O
station