Power Supply Wiring; Ac Power Supply Wiring - Mitsubishi Electric MELSEC iQ-F Series User Manual

Programmable
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

13.4

Power Supply Wiring

AC power supply wiring

• Connect the AC power supply to the [L] and [N] terminals (common for 100VAC system and 200VAC system).
• Note that the power of the powered input/output module is turned on at the same time as the CPU module or earlier than
the CPU module.
• Some expansion adapter and intelligent function modules may not have power supply terminals.
When using an external power supply, turn on the power supply at the same time as the CPU module or earlier than the
CPU module. When turning off the power, check the safety of the system and turn off the power of the programmable
controller (including extension devices) at the same time.
• Do not connect the [24V] terminals (24VDC service power supply) of the CPU module and the powered input/output
module with each other. Connect the [0V] terminal.
• When using an extension power supply module, pull out the power cable and ground wire above the product as shown
below.
Ground cable
and power
cable
When using a safety extension module, power on all the modules at the same time.
If all the modules cannot be powered on simultaneously, power them on in the following order: the modules
other than the safety extension module/CPU module
When the above condition is not satisfied, an error (error code: 3052H) may occur in the safety extension
module.
For details on wiring, refer to the following.
MELSEC iQ-F FX5 User's Manual (Safety Control)
*1 The "modules other than the safety extension module/CPU module" are as follows.
Powered input/output module, extension power supply module, expansion adapter, and intelligent function module
13 WIRING
172
13.4 Power Supply Wiring
*1
, CPU module, and safety extension module.

Advertisement

Table of Contents
loading

Table of Contents