• Cables
-Make sure to use shielded cables as cables pulled out of the control panel.
-Connect the shield such as shielded cables and shielding covers to the grounded control panel.
• It is possible that the accuracy temporarily fluctuates within 10%.
Perform the following when using the FX5-4AD-ADP:
• Set the number of times of winding to "2 turns" within approximately 200mm from terminal block of the analog cable on the
FX5-4AD-ADP side, and attach a ferrite core. (Ferrite core used in test by Mitsubishi Electric: E04SR401938 manufactured
by SEIWA ELECTRIC MFG. CO., LTD.)
Perform the following when using the FX5-4DA-ADP:
• Set the number of times of winding to "2 turns" within approximately 200mm from the connectors of the power cable on the
FX5-4DA-ADP side, and attach a ferrite core. (Ferrite core used in test by Mitsubishi Electric: E04SR401938 manufactured
by SEIWA ELECTRIC MFG. CO., LTD.)
• The FX5-4A-ADP requires that the cable used for power supply is 30m or less.
Perform the following when using the FX5-4A-ADP:
• Attach a ferrite core to the CPU module and the power supply of the FX5-4A-ADP. Set the number of times of winding to "2
turns" and attach the ferrite core within approximately 200mm from the terminal block and the connector of the power cable.
(Ferrite core used in test by Mitsubishi Electric: E04SR401938 manufactured by SEIWA ELECTRIC MFG. CO., LTD.)
• The FX5-4A-ADP requires that the cable used for power supply is 30m or less.
• For 24VDC power supply of the FX5-4A-ADP, supply power from the AC/DC power supply in the same control panel. (AC/
DC power supply used in test by Mitsubishi Electric: PS5R-VE24 manufactured by IDEC Corporation)
■Caution for when the built-in Ethernet port is used
• Use a shielded twisted pair cable for the 10BASE-T or 100BASE-TX cable. Strip a part of the jacket of the shielded twisted
pair cable as shown below and ground as much of the exposed shield as possible to both sides of the cable.
• Connect a ferrite core to both ends of the cable. (Ferrite core used in test by Mitsubishi Electric: ZCAT2035-0930A
manufactured by TDK Corporation)

Compliance with UKCA marking

The requirements for compliance with the UKCA marking are the same as those for the EC directive (CE Marking).
APPX
270
Appendix 2 Standards
Shield
Clamp fitting
Ferrite core